QTHS Series SF6 Gas Recovery Equipment
The QTHS series of SF6 gas recovery equipment is capable of evacuating and recharging SF6 gas to electrical equipment. And it also recovers or collects SF6 gas in electrical equipment and then filters, purifies, and condenses SF6 gas into storage tanks. The recycling machine is suitable for SF6 electrical appliances, GIS composite equipment, etc. The equipment is produced by Chongqing Yuneng Oil Purifier Machine Manufacturing Co., Ltd.
Share to
The Product Configuration:
- The machine has SF6 switches and GIS evacuation and vacuum readings.
- The QTHS series SF6 gas recovery and refilling device is also equipped with evacuation and vacuum readings of the liquefied gas tank.
- There are also evacuation and vacuum readings of the device itself.
- The device can charge the SF6 switch.
- If the customer wants to recover SF6 gas from electrical equipment, remove the water and oil content.
- The equipment can also dry and purify the recovered SF6 gas.
- The liquefied SF6 gas operation is carried out after the gas is recovered.
- Store the liquefied SF6 gas in a tank.
- The machine injects SF6 gas into the outer tank.
- The purification system can be regenerated after a period of use.9. inject SF6 gas into the outer tank.
Application of SF6 Gas Recovery Unit:
QTHS series SF6 gas recovery unit evacuates and then charges SF6 to the electric device. It also collects and recycles SF6 gas from the electric appliance, then purifies and condenses SF6 gas to the storage tank. This recycling machine applies to SF6 electric appliances and GIS composite apparatus, etc. The system includes recovery, charging, evacuation, purification, and gas storage.
The purification system can be regenerated after a period of use.9. inject SF6 gas into the outer tank.
In addition to SF6 purification devices, we also provide various oil filtration equipment, such as transformer oil and turbine oil purifiers, etc.
Parameters of SF6 Gas Recovery Unit:
Type | High pressure liquefaction, air cool, mobile | |
Working Environmental Temperature | -10℃ ~ 40℃ | |
Recovery | Initial pressure | 0.8 |
Final pressure (MPa) | ≤0.05 | |
Time to recover 1m3 gas(h/m) | ≤0.5 | |
Filling | Initial pressure | ≤133 |
Final pressure (MPa) | 0.8 | |
Time to recover 1m3 gas(h/m) | ≤0.5 | |
Time for pumping vacuum from 0.1Mpa to 133Pa(h/m) | ≤1 | |
Limit vacuum (Pa) | ≤10 | |
Gas purity after recovery SF6 (50KGS) | Water content(PPM/V) | ≤60 |
Oil content (PPM/W) | ≤5 | |
Dust(Micron) | ≤1 | |
Storing Tank | Storage method | Liquid gas |
Pressure (MPa) | ≤5.0 | |
Volume (L) | 300 | |
Liquid volume(Kg) | 280 | |
Liquefaction method | High pressure liquefaction | |
Vaporization method | Heating with electricity | |
Dry filter regeneration | Vacuum heating re-activated | |
Power | 380V 50Hz 3 Phase 4 Wire (based on your requirement) | |
Overall dimension | mm | 1600*1000*1900 (including the storing tank) |
1600*1000*1200 (without the storing tank) | ||
Total power (KW) | ≤8 |